 MEDIUM VOLTAGE CURRENT LIMIT REACTORS
DATA SHEET

During the switch of a capacitor bank, the switching transient current is very high. The current can even be very close to the short circuit current level. By mounting a current limiting reactor to the system, the switching transient current can be reduced to a much more safer level. As a result, circuit breaker will be protected.

 

 MEDIUM VOLTAGE CURRENT LIMIT REACTORS TECHNICAL DATA

Standarts
Design
Rated Voltage
Rated Current
Rated Frequency
Protection Class
Insulation Class
Heating
Cooling
Ambient Temperature
Phase Number
Tolerance of Inductance
Humidity
Winding
Terminal

: EN60289
: Air cored Dry type
: 6,3kV……………36kV
: 30A………….250A
: 50Hz
: IP00
: F Class 1550C
: Max. 120 C
: Natural T40
: 40 C
: 1 phase (single or tower configuration)
: +20%
: 95%
: Copper, Aluminium
: Aluminium or copper bar

 MEDIUM VOLTAGE CURRENT LIMIT REACTORS DATA SHEET PAGE HEAD 